ZDL-2B1-12Z3

https://www.bellwin.com.tw/web/image/product.template/74/image_1920?unique=254c877

DigiPDU ZDL-2 supports power control, temperature monitoring, web page management, message, e-mail, and SNMP functions together, supports SNMP (V1/V2/V3) and SNMP Trap, Web API (JSON format control) to enable MIS staff to be informed with the power supply, external temperature of equipment, and thereby to remotely deal with the relevant problems through Internet. In this way, problems can be solved at the earliest, helping to reduce the losses of enterprises, while MIS staff can save time without commuting between two places.

Not Available For Sale

  • Voltage
  • Current
  • Socket
  • Socket / Number
  • Plug
  • Materials
  • Rack Form

This combination does not exist.

Voltage: 100-120V
Current: 15A
Socket: NEMA 5-15R
Socket / Number: 2
Plug: separated power cord-IEC60320-C14
Materials: Iron Case
Rack Form: 19" standard racks (1U)

Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days




Product Features

  • IP addressable to allow administrator manage equipment from remote sites.
  • Warning by Email and SMS to bring environment real-time monitoring and warning come true.
  • Support set of power sequence startup, prevent all outlets from power on at the same time which may result in an instant overload to affect the device operation.
  • Provide multi-group account numbers so that different users can control different power switch.
  • Record the user operation information and alert information for future inquiry.
  • Support online firmware upgrade to renew equipment functions.
  • Protected by overload current circuit breaker and prevent the damage of overload.
  • Support power schedule to set up appropriate working schedule.
  • Support IP and MAC filter to prevent unauthorized user access to devices.
  • SNMP V1/V2C/V3, can monitor the cabinet monitoring host status by SNMP View program.
  • Support SNMP Trap.
  • Support Web API (JSON format control) and SNMP control, administrators can integrate their own programs.
  • Support http encrypted data transmission.
  • Support email encryption (for instance, Gmail, Hotmail).
  • Built-in temperature sensor, available to connect external temperature sensor.
  • Support Real Time Clock (RTC).




Specifications

Input Voltage

100 - 120 VAC

Maximum Input Current

12A (Maximum)

Standby Mode

5W

Power Frequency

50 / 60 Hz

Plug Type

IEC 60320 C14

Input Power

2880 VA

Socket Type

1U 2 Port

NEMA 5-15R*2

Branch : 1 - 2

Output Voltage

100 - 120 VAC

Max Output Current(Socket)

NEMA 5-15 : 15A(Maximum)

Max Output Current (Circuit)

12A (Maximum)

Max Output Current (Total)

12A (Maximum)

Metering Precision

Current Error Rate : 1%

MaterialsIron Case

Rack Form

19" standard racks (1U)

Dimension Unit : mm

180(L)*124(W)*44(H)

Weight


Power Cord Length

1.8 M

Temperature(Operating / Storage)

0° - 45° C / 0° - 60° C

Humidity(Operating / Storage) 0 - 90% No Condensation


Diagram


DM

ZDL-2B1-12Z3_中​​ 

ZDL-2B1-12Z3_En ​

全系列-DM_Tw

Series-DM_En ​


Operation Manual

ZDL-2系列-使用手冊-中文 

ZD Series- manual-en 


Accessories